kohler genset 4CZ23

Status
Not open for further replies.

iisinc

Cadet
Joined
May 6, 2004
Messages
27
This genset will not keep running after start switch is returned to the run position. I have check all emergency shutoff senders (i.e.high temp, low oil pressure etc...). I think there is a rectifier that turns the AC from genset to DC 12 volts to keep the genset running after it starts to generate AC current. How can I keep the genset running (maybe jump the ignition directly to 12 volts)? I am going to get the repair manual for this model soon. Does the exciting capacitor have something to do with this problem? I sure hope someone out there is familiar with this problem. Any help will be deeply appreciated. Thanks,<br /><br />Steve R.
 

Capt Ken

Commander
Joined
Jul 30, 2002
Messages
2,270
Re: kohler genset 4CZ23

This unit is a capacitor regulated system. The most common problem is low rpms which is hard to notice. The unit has a honey spot in which it makes electricity. Just below that spot, no power. What you will need to do is connect a voltmeter to the AC output and check the voltage when starting. If no voltage or very little is present, move the governor arm with your finger and pick the rpms up a bit. If the voltage comes up on the gauge, you have found your problem. You will then need to readjust the governor.
 

Contour

Recruit
Joined
Oct 15, 2007
Messages
2
Re: kohler genset 4CZ23

check ffraboni's thread and the reply he got. Similar problem turned out to be a dirty carb I guess! Good Luck!
 

Haut Medoc

Supreme Mariner
Joined
Jun 29, 2004
Messages
10,645
Re: kohler genset 4CZ23


Hmmmm.....
3.5 year old thread, hope he figgered it out by now.......:rolleyes:
 

seawolf5

Recruit
Joined
Jan 21, 2010
Messages
1
Re: kohler genset 4CZ23

:)
This genset will not keep running after start switch is returned to the run position. I have check all emergency shutoff senders (i.e.high temp, low oil pressure etc...). I think there is a rectifier that turns the AC from genset to DC 12 volts to keep the genset running after it starts to generate AC current. How can I keep the genset running (maybe jump the ignition directly to 12 volts)? I am going to get the repair manual for this model soon. Does the exciting capacitor have something to do with this problem? I sure hope someone out there is familiar with this problem. Any help will be deeply appreciated. Thanks,<br /><br />Steve R.

I fix my yesturday, same problem. Checks de electric elements in the control box and found out that the large capasitor 20uf 440 VAC was not working, bought a similar model at an electric shop ($4) plugged in and it run as good as always.
Good luck
seawolf5
 

Bondo

Moderator
Staff member
Joined
Apr 17, 2002
Messages
71,148
Re: kohler genset 4CZ23

Ayuh,...Seawolf,... Welcome Aboard,....

This thread is older than Dirt....
Please Don't reply to the antiques from the archives...

I gotta belive the OP fixed his generator about 5 or 6 Years ago...
 